HVAC
HEATING
CATALOG
NOW AVAILABLE
780U SERIES UNIVERSAL
IGNITION MODULES
780U-DS20 DIRECT SPARK
780U-IP10 INTERMITTENT PILOT
780U-HS30 HOT SURFACE IGNITION
•
Highly configurable 24V modules
•
Optimized for gas furnaces, water heaters, commercial cooking equipment, and unit heaters
•
Up to 32 preloaded configurations for easy installation
•
Replaces over 700 part numbers
•
Simplifies inventory management
•
Ensures seamless operation across various replacement models
Learn More
Scan for instant access to OEM cross-reference details
Learn More
Learn More
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
TABLE OF CONTENTS
WALL THERMOSTATS
NEW Pro-Series Manual/Programmable,
Single-/Multi-Stage Heating/Cooling ............................................................ 2
800 Series Line Voltage ..................................................................................... 4
9200 Series Deluxe Mechanical....................................................................... 4
RS1000 Series Economy Digital ...................................................................... 5
HUMIDISTATS AND DEHUMIDISTATS
J10 Series ............................................................................................................ 5
GAS VALVES
700 Series Universal Gas Valves - Intermittent Pilot,
Direct Spark or Hot Surface ............................................................................. 6
700 Series Millivolt Gas Valves ........................................................................ 6
700 Series 24 Volt Combination Gas Valves ................................................. 8
700 Series Diaphragm/Solenoid Gas Valves ................................................ 9
700 Series Universal 2-Stage 24 Volt Gas Valves .......................................... 10
700 Series Snap-Action and Snap-Throttle
Gas Valves ........................................................................................................... 10
705 Series Gas Actuators .................................................................................. 11
710 Series Low Capacity Gas Valves .............................................................. 12
720 Series 24 Volt Dual Gas Valves ................................................................. 13
720 Series Lever-Actuated Gas Valves ........................................................... 14
110 Series Water Heating Gas Valves ............................................................. 15
ELECTRIC THERMOSTATS
5600 Series Water Heating Electric Thermostats ........................................ 16
WH9 Series Electric Thermostats ................................................................... 16
HEATING KITS
710-296 Millivolt Heating Kit............................................................................ 17
712 Series Intermittent Pilot Ignition System Kits ...................................... 17
785 Series Automatic Pilot Relight Kits ......................................................... 18
REGULATOR KITS
1751 Series Pressure Regulators .................................................................... 19
WIRING HARNESSES
1751 Series Wiring Harnesses ......................................................................... 20
IGNITION CONTROLS
NEW 780U Series Universal Ignition Controls .............................................. 20
780 Series Ignition Controls ............................................................................ 21
790 Series Ignition Controls ............................................................................ 23
35 Series Ignition Controls............................................................................... 23
05-29 Series Direct Spark Ignition Controls.................................................. 24
05-30 Series Direct Spark Ignition Controls.................................................. 25
FAN CONTROLS
695 Series Electronic Fan Controls ................................................................ 25
TRANSFORMERS
620 Series Transformers ................................................................................... 25
IGNITORS
Universal Silicon Nitride Hot Surface Ignitors ............................................. 27
41-400 Series Silicon Carbide Hot Surface Ignitors .................................... 27
41-600 Series Silicon Nitride Hot Surface Mini-Ignitors ............................. 29
NEW OEM Direct Replacement Silicon Nitride Ignitors .............................. 29
PILOTS
1800 Series Pilots ............................................................................................... 30
1820 Series Pilot Uni-Kits ................................................................................. 30
1830-700 Series Pilot Uni-Kits ......................................................................... 31
1830 Series Electronic Pilot Burner with
Safety Switch ...................................................................................................... 33
1830 Series Pilot Uni-Kits ................................................................................. 33
Universal Pilot Mounting Ignitor Sensors ..................................................... 36
THERMOCOUPLES
1900 Series Thermocouples ............................................................................ 36
1960 Series Thermocouples ............................................................................ 36
1970 Series Thermocouples ............................................................................ 37
1980 Series Snap-Fit® Thermocouples ......................................................... 37
THERMOPILES
1950 and 1951 Thermopiles ............................................................................ 38
SURGE PROTECTION DEVICES
Surge-Trap Series Surge Protective Devices................................................. 39
AIR PRESSURE SENSING SWITCHES
Air Pressure Sensing Switch Series ................................................................ 39
FIREPLACE CONTROLS
Gas Valves ........................................................................................................... 41
Remote Controls ................................................................................................ 41
Timers .................................................................................................................. 42
Universal Fan Kits .............................................................................................. 42
ACTUATORS
SmartX PIBCV Valves and Actuators Series .................................................. 43
Smart PIBCV Actuators Series ......................................................................... 43
Erie® PopTop Two-Position Zone Valves and Actuators Series ................ 44
ELECTRODE/SENSOR ASSEMBLIES
Electrode/Sensor Assemblies ......................................................................... 45
FLAME SENSORS
NEW Heating Sensors Series ........................................................................... 45
HEATING ACCESSORIES
190 Series Wall Thermostat Guard Kits ......................................................... 46
Heating Shank Extension Series ..................................................................... 46
Heating Dial Series ............................................................................................ 46
Heating Adaptor Series .................................................................................... 47
Energy Cut Off Switch Wire Assembly Series ............................................... 47
Cable and Harnesses ........................................................................................ 48
Pilot Orifices Series ........................................................................................... 48
Unitrol Replacement Gasket Series ............................................................... 48
4590 Series Plugs ............................................................................................... 49
4590 Series Breakaway Ferrules ..................................................................... 49
10-600 Series Electronic Fan Controls ........................................................... 50
Service Products and Parts .............................................................................. 50
APPENDIX ............................................................................................................ 51
INDEX ................................................................................................................... 54
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
WALL THERMOSTATS
NEW Pro-Series Manual/Programmable, Single-/Multi-Stage Heating/Cooling
Ten-model.series.minimizes.inventory,.yet.controls.nearly.all.gas-,.electric-.or.oil-fueled.single-stage.and.multi-stage.heating.and.cooling.system.confi.gurations..
Off.ers.manual,.5-1-1.programmable.and/or.7-day.programmable.control,.varying.by.model..All.models.suit.heat.pumps.and.several.suit.auxiliary/emergency-capable.
heat.pumps..Several.models.off.er.both.hardwire.and.battery.power..Includes.a.WiFi/smartphone.accessible.model.
Part
Number
Description
Heat Pump
Compatibility
Power Source(s)
Dimensions
Display
Control Features
Terminals
RS8110
Wall Thermostat –
Non-Programmable,
1 Heat, 1 Cool
Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
4.6 sq. Inch Blue Backlit
Adjustable Differential
Adjustable Setpoint
Limits
Short Cycling Prevention
Rh, Rc,
C, Y,
W, G, O, B
RS8210
Wall Thermostat –
Non-Programmable,
2 Heat, 1 Cool
With or Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
4.6 sq. Inch Blue Backlit
Adjustable Differential
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
R, C, Y, W2,
W/E, G,
O, B
RS9110
Wall Thermostat –
5-1-1 and 7-day
Programmable,
1 Heat, 1 Cool
Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
4.6 sq. Inch Blue Backlit
Adjustable Differential
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
Rh, Rc,
C, Y,
W, G, O, B
RS9210
Wall Thermostat –
5-1-1 and 7-day
Programmable,
2 Heat, 1 Cool
With or Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
4.6 sq. Inch Blue Backlit
Adjustable Differential
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
R, C, Y, W2,
W/E, G,
O, B
RS9220
Wall Thermostat –
5-1-1 and 7-day
Programmable,
2 Heat, 2 Cool
Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
4.6 sq. Inch Blue Backlit
Adjustable Differential
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
Rh, Rc,
C, Y,
Y2, W, W2,
G, O, B
RS9110T
Wall Thermostat –
5-1-1 and 7-day
Programmable,
1 Heat, 1 Cool
Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
8.8 sq. Inch Blue Backlit
Touchscreen
Adjustable Differential
Auto Changeover
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
Keypad Lockout
Rh, Rc,
C, Y,
W, G, O, B
RS9320T
Wall Thermostat –
5-1-1 and 7-day
Programmable,
3 Heat (Heat Pump),
2 Cool (No Heat Pump)
With or Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
8.8 sq. Inch Blue Backlit
Touchscreen
Adjustable Differential
Auto Changeover
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
Keypad Lockout
Rh, Rc,
C, Y,
Y2, W/E,
W2,
G, O, B
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
Part
Number
Description
Heat Pump
Compatibility
Power Source(s)
Dimensions
Display
Control Features
Terminals
RS9423T
Dual Fuel Compatible
Wall Thermostat –
5-1-1 and 7-Day
Programmable, 4 Heat
(Heat Pump), 2 Cool
(No Heat Pump)
With or Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
DC 2 x AAA 1.5V
Alkaline Batteries
(Included)
4.7" W x 3.8" H x 1" D
8.8 sq. Inch Blue Backlit
Touchscreen
Dual Fuel Compatible
Wireless Balance Point
for Heat Pumps
Compatible With
RS9055OUT Remote
Sensor
Adjustable Differential
Auto Changeover
Adjustable Setpoint
Limits
Short Cycling Prevention
Filter Change Reminder
Keypad Lockout
Rc, Rh, C,
B, O, G,
W/E, Y, Y2,
W2
RS10420T
WiFi/Smartphone
Accessible Wall
Thermostat – 7-Day
Programmable, 4 Heat
(Heat Pump), 2 Cool
(No Heat Pump)
With or Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
4.7" W x 3.8" H x 1" D
8.8 sq. Inch Blue Backlit
Touchscreen
WiFi/Smartphone
Accessible
Adjustable Differential
Auto Changeover
Adjustable Setpoint
Limits
Short Cycling Prevention
Rh, Rc,
C, Y,
Y2, W/E,
W2,
G, O, B
RS10421T
WiFi/Smartphone
Accessible Wall
Thermostat with
Humidifi cation/
Dehumidifi cation
Control – 7-Day
Programmable, 4 Heat
(Heat Pump), 2 Cool
(No Heat Pump)
With or Without Aux/
Emergency Heat
24V Hardwire
(C Terminal)
4.7" W x 3.8" H x 1" D
8.8 sq. Inch Blue Backlit
Touchscreen
WiFi/Smartphone
Accessible
Humidifi cation/Dehu-
midifi cation Control
Compatible With
RS9055OUT Remote
Sensor
Adjustable Differential
Auto Changeover
Adjustable Setpoint
Limits
Short Cycling Prevention
Rh, Rc,
C, Y,
Y2, W/E,
W2,
G, O, B,
H, D
WALL THERMOSTAT ACCESSORIES
Part Number
Description
Compatible Thermostats
Power Source(s)
Features
RS9055OUT
Wireless Outdoor
Temperature Sensor
RS9423T, RS10421T
Battery Powered
Senses Outdoor Temperatures
Use for Dual Fuel Heat Pump Balance Point
Applications
Durable Weatherproof Design
RS9010-2
Wall Plate
All Pro-Series Thermostats
NA
Bright White Color
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
WALL THERMOSTATS
800 Series Line Voltage
Universal.replacements/retrofi.ts.for.many.other.brands,.mercury-free.800.Series.line.voltage.thermostats.need.no.leveling.or.special.disposal..
They.feature.bimetal.temperature.sensing.and.are.accurate.to.within.+/-2°F..J-Box.compatible,.these.units.meet.code.and.install.quickly.
Part
Number
Description
Heat/Cool
Voltage
Electrical Rating
Switch Action
Temperature Control
Range
Control Features
801
Line Voltage
Thermostat - Heat
SPST Switch
Action
Heat
120 / 240 / 277
25 AMP at 250 VAC RES
18 AMP at 277 VAC RES
1 HP at 125 VAC
2 HP at 250 VAC
125 VA PILOT DUTY
SPST
50ºF to 90ºF
(10ºC to 32ºC)
Convenient At-a-Glance
Temperature Display
Bimetal Temperature Sensing
Positive-Off Switch Ensures
System Shutdown
802
Line Voltage
Thermostat - Heat
DPST Switch
Action
Heat
120 / 240 / 277
25 AMP at 250 VAC RES
18 AMP at 277 VAC RES
1 HP at 125 VAC
2 HP at 250 VAC
125 VA PILOT DUTY
DPST
50ºF to 90ºF
(10ºC to 32ºC)
Convenient At-a-Glance
Temperature Display
Bimetal Temperature Sensing
Positive-Off Switch Ensures
System Shutdown
803A
Line Voltage
Thermostat - Cool
DPST Switch
Action
Cool
120 / 240 / 277
25 AMP at 250 VAC RES
18 AMP at 277 VAC RES
1 HP at 125 VAC
2 HP at 250 VAC
125 VA PILOT DUTY
SPST
50ºF to 90ºF
(10ºC to 32ºC)
Convenient At-a-Glance
Temperature Display
Bimetal Temperature Sensing
Positive-Off Switch Ensures
System Shutdown
WALL THERMOSTATS
9200 Series Deluxe Mechanical
9200.Series.Deluxe.Mechanical.thermostats.replace.more.than.50.competitive.models.and.potentially.minimize.inventory.space..
Also,.with.no.sub-base.or.leveling.required.and.a.simple.base.and.cover.design,.they.install.quickly..Horizontal.and.vertical.designs.are.available.
Part
Number
Description
Stage
Control
Electrical Rating
Switch
Action
Temperature
Control Range
Anticipation
Installation and Control
Features
Installation and
Control Features
9200H
Deluxe
Mechanical
Thermostat
– 1 Heat, 1 Cool,
Horizontal Design
1 Heat
1 Cool
24V AC (18 to 30V AC)
2 Amp Maximum /
240 to 750 Millivolts
SPDT
50°F to 90°F
(10°C to 32°C)
Fixed 0.2 to 1.6 Amps
(24V)
Fixed 1.8 Amps
(240 to 750 mV)
Fixed 4700 ohms
(Cooling)
Two-Piece Design
Wall-Mountable Base
J-Box-Compatible
Heavy-Duty Adjustable
Heat Anticipator
W, Y, O, G, Rc, Rh, B
9200V
Deluxe
Mechanical
Thermostat
– 1 Heat, 1 Cool,
Horizontal Design
1 Heat
1 Cool
24V AC (18 to 30V AC)
2 Amp Maximum /
240 to 750 Millivolts
SPDT
50°F to 90°F
(10°C to 32°C)
Fixed 0.2 to 1.6 Amps
(24V)
Fixed 1.8 Amps
(240 to 750 mV)
Fixed 4700 ohms
(Cooling)
Two-Piece Design
Wall-Mountable Base
J-Box-Compatible
Heavy-Duty Adjustable
Heat Anticipator
W, Y, O, G, Rc, Rh, B
9204H
Deluxe
Mechanical
Thermostat
– Heat Only,
Horizontal Design
1 Heat
24V AC (18 to 30V AC)
2 Amp Maximum /
240 to 750 Millivolts
SPST
50°F to 90°F
(10°C to 32°C)
Fixed 0.2 to 1.6 Amps
(24V)
Fixed 1.8 Amps
(240 to 750 mV)
Two-Piece Design
Wall-Mountable Base
J-Box-Compatible
Heavy-Duty Adjustable
Heat Anticipator
W, Rh
9204V
Deluxe
Mechanical
Thermostat
– Heat Only,
Vertical Design
1 Heat
24V AC (18 to 30V AC)
2 Amp Maximum /
240 to 750 Millivolts
SPST
50°F to 90°F
(10°C to 32°C)
Fixed 0.2 to 1.6 Amps
(24V)
Fixed 1.8 Amps
(240 to 750 mV)
Two-Piece Design
Wall-Mountable Base
J-Box-Compatible
Heavy-Duty Adjustable
Heat Anticipator
W, Rh
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
Universal.replacements/retrofi.ts.for.many.other.brands,.mercury-free.800.Series.line.voltage.thermostats.need.no.leveling.or.special.disposal..
They.feature.bimetal.temperature.sensing.and.are.accurate.to.within.+/-2 F..J-Box.compatible,.these.units.meet.code.and.install.quickly.
9200.Series.Deluxe.Mechanical.thermostats.replace.more.than.50.competitive.models.and.potentially.minimize.inventory.space..
Also,.with.no.sub-base.or.leveling.required.and.a.simple.base.and.cover.design,.they.install.quickly..Horizontal.and.vertical.designs.are.available.
WALL THERMOSTATS
RS1000 Series Economy Digital
RS1000.Economy.Series.battery.powered.manual/5-1-1.programmable.thermostats.are.designed.as.aff.ordable.options.in.
new.or.replacement.residential.applications..They.can.be.confi.gured.to.control.conventional.gas.or.electric.HVAC,.heat.
pump,.oil.and.millivolt.equipment.in.either.Fahrenheit.or.Celsius..They.off.er.control.accuracy.of.+/-1°F.@.68°F.(0.5°C.@.20°C).
Part
Number
Description
Heat/Cool
Confi guration
Power
Source
Temperature
Control Range
Relay Contact
Voltage
Relay Contact
Current
Dimensions
Control Features
Terminations
RS1110
Economy Battery
Operated Manual/
Programmable
Thermostat
4-wire
1 Heat/1 Cool
Conventional
Gas/Electric
or Heat Pump
3V DC
(2 x AAA
Alkaline
Batteries)
Heating:
40° to 90°F
(5° to 32°C)
in 1° Steps
Cooling:
60° to 95°F
(16° to 35°C)
in 1° Steps
24V AC / 50/60 Hz 1 Amp Maximum
(Inductive)
3.35" H x 4.5" W
x 1" D
(85mm H x 114mm W
x 26mm D)
Manual or 5-1-1 Programmable
Fahrenheit or Celsius
Adjustable Temperature Differential
Compressor Short-Cycling Protection
Worry-Free Memory Retention for
Power Outages
R – 24V
Switching Voltage
G – Fan, W – Heat
or O/B O – rev.
Valve in Cooling
B – Rev. Valve
in Heating
HUMIDISTATS AND DEHUMIDISTATS
J10 Series
Ranco®.J10.Series.Humidistats.and.Dehumidistats.regulate.relative.humidity.in.confi.ned.spaces.by.cycling.centralized.humidifying.or.dehumidifying.systems..The.
nylon.sensing.element.provides.fast.response.time,.accurate.control.and.long.life.
Part Number
Description
Humidity Range
Electrical Rating
Temperature Range
Differential
J10-808
Humidistat – Wall or Duct Mount
10% to 60% Relative Humidity
24V AC/60V AC
Switch Head 32°F to 140°F
(0°C to 60°C)
5% or 15% RH
J10-809W
Dehumidistat – Wall Mount
20% to 80% Relative Humidity
24V AC/60V AC
Switch Head 32°F to 140°F
(0°C to 60°C)
5% or 15% RH
J10-810
Dehumidistat – Wall Mount
(Vertical)
20% to 80% Relative Humidity
24V AC/60V AC
Switch Head 32°F to 140°F
(0°C to 60°C)
5% or 15% RH
J10-821
Humidistat – Wall Mount
(Horizontal)
20% to 80% Relative Humidity
24V AC/60V AC
Switch Head 32°F to 140°F
(0°C to 60°C)
5% or 15% RH
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
RoHS
GAS VALVES
700 Series Universal Intermittent Pilot Gas Valves – Direct Spark or Hot Surface
Incorporating.all.the.necessary.parts.to.adapt.to.direct.spark.or.hot-surface.applications,.these.universal.replacement.valves.provide.
intermittent.pilot.ignition.in.central.heating.units,.wall.heaters,.boilers,.mobile.home.furnaces.and.more..Each.valve.is.equipped.with.a.
manual.valve,.pilot.valve.and.a.main.gas.pressure.regulator.(optional.by.model).
Part
Number
Factory
Part Number
Description
Capacity
Electrical Rating
Inlet
Size
Outlet
Size
Pressure
Regulation
Maximum Inlet
Pressure
Comments
700-049*
7000BDER-S7A
Universal Gas Valve
300,000 BTU
24V AC @ 60 Hz
1/2"
1/2"
3.0" WC
Natural Gas
14" WC (1/2 PSI)
Straight-thru with slow opening
feature for soft ignition. Can be fi eld
removed. Includes pilot plug
700-056*
7000BDER-S7A
Universal Gas Valve
350,000 BTU
24V AC @ 60 Hz
3/4"
3/4"
3.5" WC
Natural Gas
14" WC (1/2 PSI)
Straight-thru. Has slow opening
feature for soft ignition.
Can be fi eld removed
700-057
7000DERHC
Universal Gas Valve
720,000 BTU
24V AC @ 60 Hz
1"
1"
4.0" WC
Natural Gas
14" WC (1/2 PSI)
Straight-thru
700-059*
7000DERHC-S7C
Universal Gas Valve
720,000 BTU
24V AC @ 60 Hz
1"
1"
4.0" Natural
Gas
14" WC (1/2 PSI)
Straight-thru with slow opening
feature for soft ignition.
Can be fi eld removed.
RoHS
GAS VALVES
700 Series Millivolt Gas Valves
Robertshaw®.700.Series.Millivolt.Gas.Valves.are.wall.thermostat.actuated.combination.controls.for.millivolt.applications.ranging.from.furnaces.to.swimming.pools..
These.700-500.millivolt.gas.valves.off.er.installation.fl.exibility,.covering.a.wide.range.of.replacement.from.small.capacity.3/8”.pipe.to.high.capacity.1”.pipe.and.up.to.
720,000.BTUs.
Part
Number
Factory
Part Number
Description
Capacity
Electrical
Rating
Inlet
Size
Pressure
Regulation
3 Position Outlet
Straight-Thru (FPT)
Reducer
Bushing
(NPT)
Comments
359811491A
7000BMVR
Millivolt
Gas Valve
300,000 BTU
250mV to
750mV
3/4"
3.5" WC
Natural Gas
NA
700-501
7000AMV
Millivolt
Gas Valve
100,000 BTU
250mV to
750mV
1/2"
None
1/2"
700-502
7000AMVR
Millivolt
Gas Valve
100,000 BTU
250mV to
750mV
1/2"
3.5" WC
Natural Gas
1/2"
Coaxial thermopile and
2 lead thermopile can
be used
* Cross Reference: Robertshaw - 700-049 = White-Rodgers - 36H32-214; Robertshaw - 700-056 = Honeywell - VR8204M1018, VR8204M1034, VR8204M1083
and White-Rodgers - 36C68-404, 36C68-423, 36C74-313; Robertshaw - 700-059 = Honeywell - VR8304H3208, VR8304H3216, VR8304H3224
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
Part
Number
Factory
Part Number
Description
Capacity
Electrical
Rating
Inlet
Size
Pressure
Regulation
3 Position Outlet
Straight-Thru (FPT)
Reducer
Bushing
(NPT)
Comments
700-503
7000BMV
Millivolt
Gas Valve
240,000 BTU
250mV to
750mV
1/2"
None
3/4"
700-504
7000BMVR
Millivolt
Gas Valve
240,000 BTU
250mV to
750mV
1/2"
3.5" WC
Natural Gas
3/4"
Coaxial thermopile and
2 lead thermopile can
be used
700-505
7000BMV
Millivolt
Gas Valve
300,000 BTU
250mV to
750mV
3/4"
None
3/4"
700-506
7000BMVR
Millivolt
Gas Valve
300,000 BTU
250mV to
750mV
3/4"
3.5" WC
Natural Gas
3/4"
Coaxial thermopile and
2 lead thermopile can
be used
700-507
7000BM
VR-S7C
Millivolt
Gas Valve
240,000 BTU
250mV to
750mV
1/2"
3.5" WC
Natural Gas
3/4"
Slow opening feature for
soft ignition
700-508
7000BMVR
Millivolt
Gas Valve
240,000 BTU
250mV to
750mV
1/2"
3.5" WC
Natural Gas
3/4"
700-511
7000BM
VRFT-S7C
Millivolt
Gas Valve
400,000 BTU
250mV to
750mV
3/4"
4.0" WC
Natural Gas
plus Uni-Kit for
LP Gas
3/4"
Teledyne-Lars coaxial
thermopile and 2 lead
thermopile can be used.
Slow opener
700-513
7010BGVMV
Millivolt
Gas Valve
240,000 BTU
250mV to
750mV
1/2"
None
1/2"
Diaphragm valve
only-no gas cock or
safety magnet.
700-515
7000BMVR-LP
Millivolt
Gas Valve
485,000 BTU
250mV to
750mV
3/4"
10.0" WC LP
Gas
3/4"
700-516
7000BMVR
Millivolt
Gas Valve
240,000 BTU
250mV to
750mV
1/2"
4.0" WC
Natural Gas
1/2"
NA
700 Series Millivolt Gas Valves – Continued
HEATING
Customer Service 800.304.6563 | HVACCustomerService@robertshaw.com | Robertshaw.com
Part
Number
Factory
Part Number
Description
Capacity
Electrical
Rating
Inlet
Size
Pressure
Regulation
3 Position Outlet
Straight-Thru (FPT)
Reducer
Bushing
(NPT)
Comments
700-522
7000MVRHC-
S7C
Millivolt
Gas Valve
720,000 BTU
250mV to
750mV
1"
3.5" WC
Natural Gas
1"
Slow opening feature
for soft ignition
RoHS
GAS VALVES
700 Series 24 Volt Combination Gas Valves
Featuring.three-position.outlets.and.multi-positional.capability.and.with.capacities.up.to.720,000.BTU,.Robertshaw®.700.Series.24.Volt.
Combination.Gas.Valves.off.er.unlimited.replacement.possibilities..The.valve.is.factory.set.at.3.5”.WC.natural.gas..A.regulator.cover.plate.is.
included.to.convert.to.LP.gas..Three.24.Volt.Uni-Kit®.models.suit.either.natural.or.LP.gas.applications.
Part
Number
Factory
Part Number
Description
Capacity
Electrical Rating
Inlet
Size
Outlet
Size
Pressure
Regulation
Reducer
Bushing
(NPT)
Side Outlets
Comments
700-400
7000BER
24 Volt
Combination
Gas Valve
240,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
1/2"
3/4"
Uni-Kit
Straight-Thru
700-401
7000BE
24 Volt
Combination
Gas Valve
240,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
1/2"
3/4"
None
1/2"
700-402
7000BER
24 Volt
Combination
Gas Valve
240,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
1/2"
3/4"
Uni-Kit
1/2"
700-406
7000BER
24 Volt
Combination
Gas Valve
300,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
3/4"
3/4"
Uni-Kit
Straight-Thru
700-409
7000BMSER
24 Volt
Combination
Gas Valve
240,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
1/2"
1/2"
3.5" WC
Natural Gas
Straight-Thru
Thermopile type
safety magnet
700-426
7000BER-S7A
24 Volt
Combination
Gas Valve
300,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
3/4"
3/4"
3.5" WC
Natural Gas
Straight-Thru
Slow opening feature
for soft ignition
700-428
7000BER-S7C
24 Volt
Combination
Gas Valve
300,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
3/4"
3/4"
3.5" WC
Natural Gas
Straight-Thru
Slow opening feature
for soft ignition
700-434
7000AERB-5-S7C
24 Volt
Combination
Gas Valve
100,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
1/2"
1/2"
Hi-Lo
2" - 4"
1/2"
Slow opening feature
for soft ignition
700-442
7000ERHC-S7C
24 Volt
Combination
Gas Valve
720,000 BTU
24V AC @ 0.2 Amps, 50/60 Hz
12V DC @ 0.18 Amps, 50/60 Hz
1"
1"
3.5" WC
Natural Gas
None
Straight-Thru
Slow opening feature
for soft ignition
700 Series Millivolt Gas Valves – Continued